ISO 14644標準中提出潔凈室壓差監測的要求,如下:

 

關于壓差報警限的制定,建議設定為日常監測上限-(2~3Pa)或壓差下限+(2~3Pa)

 

“After observing and recording the normal operating ranges, it is recommended that a pressure setting for the warning pressure measurement device be selected a few Pascal below the lowest pressure observation for a

positive-pressure configuration, or a few Pascal above in a negative-pressure

configuration (guidance value 2 Pa to 3 Pa).

觀察和記錄正常操作范圍后,建議對壓力報警裝置設定一個壓力報警范圍值,對于一個正壓裝置,設定所觀察到的最低壓力值-2~3Pa(建議值)作為報警值;對于一個負壓裝置,則+2~3Pa(建議值)作為報警值。

 

關于壓差報警,允許對壓差報警設定延時,以滿足日常操作需要(如進出開門),但需要合理確定該項活動所需要的時間,并以此確定延時。

 

“It is often necessary to delay the alert or action alarm to allow for normal activity in the cleanroom, such as the opening of doors to permit entry and exit of personnel. Careful observation of the duration of typical or expected normal deviation is necessary to determine appropriate time delay.Deviations that extend beyond the normal durations should activate warnings.

 

通常需要延遲報警或行動警報,以允許潔凈室的正常活動,如人員進出開關門。仔細觀察典型的或預期的正常偏差的持續時間是確定適當的時間延遲的必要條件。超出正常持續時間的偏差應激活報警。

 

有關緩沖間門的要求,除非安裝充氣密封(equipped with inflatable seals),否則開門后壓差存在泄漏(客觀事實)。

 

Air locks are designed to help maintain pressure differentials as personnel or materials move from one cleanroom or clean zone to another. Air locks are designed or operated so that one opposing door set is always closed. However, unless the doors are equipped with inflatable seals, the leakage through the airlock is usually greater when one of the opposing door sets is open than when they are both closed.

 

當人員或物料從一個潔凈室或潔凈區移動到另一個潔凈室或潔凈區時,氣閘(緩沖間)的設計有助于保持壓差。氣閘的設計或操作使一個相對的門總是關閉。然而,除非這些門裝有充氣密封,否則當其中一扇門打開時,通過氣閘的泄漏量通常比兩扇門都關閉時更大(客觀事實)。

關于緩沖間壓差的監測要求:應監測開關門后壓差恢復的情況,確保壓差恢復后才能打開另一道門。

 

It is necessary to test and document these normal variations to properly set alert and action levels for pressure alarms. Follow this procedure:

有必要測試和記錄這些(開關門)常規壓差變化,以便為壓力報警設定適當的警戒和行動限。參照以下程序進行評估:

 

close all doors and pass-through hatches, define the operational status of any equipment, and observe the steady-state pressure differentials between the selected rooms or zones noting the small, normal fluctuations that will occur due to wind and other dynamic effects;

 

關閉所有的門和傳遞窗,定義所有設備的運行狀態,觀察穩定狀態下所選擇的房間或區間的壓差,注意由于風或其它動態影響產生的小的常規波動;

 

for each airlock, pass-through hatch or transfer chamber, open allthe doors, one set of opposing doors at a time, and note room- or zone-pressurevariation. Close the doors and confirm that the pressure differentials return to theiroriginal values;

 

每個緩沖間、傳遞窗或轉移艙,打開所有的門,一次打開一邊的門,注意房間或區間壓力波動。關門,確認壓差回到其原始值;

 

leakage paths, such as those around doors, should be evaluated as part of a cleanroom design to ensure adequate allowance is made in the air balance for such leakages.

泄漏通道,例如門周邊泄漏,應進行評估,作為潔凈間設計的一部分,以確保為此泄漏做出了足夠的空氣平衡余量。